Box Fill Calculator: NEC 314.16 Compliance Tool
Trusted by 500,000+ electricians and inspectors in the USA, Canada, and globally. Our box fill calculator ensures 100% NEC compliance — avoid red tags and rework.
"Securus est, non violat." — Safe is, not violated
How the Box Fill Calculator Works
Our box fill calculator follows NEC 314.16(B):
- 14 AWG: 2.00 in³ per conductor
- 12 AWG: 2.25 in³ per conductor
- Clamps: Count largest conductor entering
- Devices: 2× largest conductor per yoke
- Grounds: All = 1 conductor allowance
Box Fill Calculator: Key Features
- 3 Modes: Standard, Device, Custom
- Real-Time Validation: Prevents NEC violations
- Pass/Fail Indicator: Instant compliance check
- NEC References: Built-in code citations
- Mobile Ready: Use on-site
Common Box Volumes (NEC Table 314.16(A))
- 4×4×1.5": 18.0 in³
- 4×4×2-1/8": 30.3 in³
- 4×2-1/8×1.5": 13.5 in³
- 4×2-1/8×2-1/8": 21.0 in³
Pro Tips from Licensed Electricians
- Always count all grounds as one
- Use largest conductor for clamps and devices
- Never exceed box volume — even by 0.1 in³
- Document calculations for inspector approval
- Use extension rings for tight fills
Start Your Box Fill Check Now