4 to 20 mA Calculator: The Global Standard for Process Control
Used by instrumentation engineers worldwide, our 4 to 20 ma calculator ensures reliable signal transmission in oil & gas, pharmaceuticals, and manufacturing.
How the 4 to 20 mA Calculator Works
Core equations:
V_drop = I × R_loop
% = (mA - 4) / 16 × 100
4 to 20 mA Calculator: Four Essential Modes
Basic Scaling Mode
Direct PV to mA conversion in our 4 to 20 ma calculator.
Voltage Drop Mode
Loop power and resistance analysis.
Loop Diagnostics Mode
Fault detection and troubleshooting.
HART & Scaling Mode
Digital HART configuration and square root extraction.
4 to 20 mA Calculator: Standard Signal Levels
| Current | % | Status |
|---|---|---|
| 0–1 mA | — | Open Circuit |
| 3.8 mA | 0% | Live Zero |
| 20.5 mA | 103.125% | Overrange |
4 to 20 mA Calculator: Loop Power Guide
- 24VDC standard — 12–36V range
- 250Ω resistor = 1–5V for PLC
- 500Ω max at 20 mA with 24V
- HART: 1200 Hz digital overlay
- IS barriers: Reduce available voltage
Pro Tips for the 4 to 20 mA Calculator
- Use shielded twisted pair cable
- Ground at one point only
- Check for ground loops with multimeter
- Calibrate at 4, 12, 20 mA
- HART: Minimum 230Ω loop resistance
Precision in Every Signal
From field to control room, our 4 to 20 ma calculator ensures zero downtime.